Molex C7A S/FTP shielded cable is specifically designed to support high-speed data network applications. The cable is constructed of four screened pairs and a tin/copper braid. The cable is designed to minimize alien crosstalk and provide superior electromagnetic interference (EMI) protection. The Category 7A cable is a complementary product for installation in the Molex PowerCat 6A system. The cable meets the transmission performance of the Category 7A 1000MHz transmission standard and is tested to 1.2MHz.
Commercial Standards
ISO 11801:2017
IEC 61156-5:2020
EN 50173:2018
EN 50288-9-1:2012
RoHS Compliant
Reaction to Fire
EU Regulation 305/2011 (CPR)
Euroclass: B2ca-s1a,d1,a1
EN 50575:2014+A:2016
Fire Propagation Tests
IEC 60332-1-1:2015
IEC 60332-1-2:2015
EN 61034-1 &2 :2019
EN 60754-1&2:2019
Mechanical
Conductor o.d.: 0.580 +/- 0.005mm
Conductor material: Solid Bare Copper
Pair Number: 4
Outer diameter: 7.8mm +/-0.5mm
Shield: Al/Mylar
Braid: Tinned copper
Temperature Range
Installation: -10°C to + 50°C
Operation: -40°C to + 75°C
Storage: -20°C to +50°C
Bend radius:
Installation: 8 x OD
Operation: 4 x OD
Pulling force: ≥8.0 Mpa
Sheath: LS0H
Sheath colour: Violet RAL 4005
Shipping weight 500m reel: 31kg
Cable length tolerance: +/- 5%
Electrical @20°C
Characteristic Impedance Ohm:
1-100 MHz: 100 +/- 15 Ω
100 -250 MHz 100 +/- 18 Ω
250-1000 MHz 100 +/- 25 Ω
DC Resistance Ω/100m max: 9.38
Resistance unbalance % max: 2.0
NVP nominal: 74%
Delay skew ns/100m max: <25