COMMERCIAL STANDARDS
ISO/IEC 11801 ISO/IEC 11801:2017
ANSI/TIA-568.2-D Cat 6A
UL, CSA pending
FIRE PROPAGATION TESTS
PVC: UL444 CM
LSZH: IEC 60332-1-1 IEC 61034-2
ENVIRONMENTAL COMPLIANCE
RoHS Compliant
MECHANICAL
Cable
Conductor Size: 26 AWG stranded copper wire
Screen Material: Aluminum/polyester shield with tinned copper drain wire
Nom. O.D.: 0.225 inch
Sheath: PVC or LSZH
Bend Radius: 8X O.D.
Operating Temperature: -20°C to +60°C
UTP RJ45 Plug
Minimum operating life: 750 insertion cycles
RJ45 Plug Material: Clear Polycarbonate (PC)
Boot Material: Clear Polycarbonate (PC)
Contact Plating: 1.27um gold
RJ45 Plug Dimensions compliant with: ISO/IEC 60603-7 and FCC 47 Part 68
ELECTRICAL
Max voltage: 150 VAC (max)
Max current: 1.5A @ 25°C
PoE
Our PowerCat 6A system is suitable for the most demanding PoE applications:
– IEEE 802.3bt from Type 1 to Type 4, and CISCO UPoE+
– HD Base-T PoH up to 100W
– RP3 compliant as defined by EN 50174-2:2018, ISO/IEC 14763-2:2019 and AS/NZS 14763.2:2020
Notes:
– For new installations of PoE Type 3 / Class 5 and above that wish to be eligible for the Molex 25 year Application Assurance Warranty, we require Category 6A cable to be used throughout.
– To confirm your PoE / RP3 cabling design is eligible for the Molex 25 year Application Assurance Warranty, your design must be verified and validated with the Molex PoE Calculator. Read more at https://www.molexces.com/poe-calculator
– Molex recommends that the PoE feature on an individual switch port is power disabled prior to unplugging the associated powered Device.
– Molex recommends that the full range of PowerCat 6A products be used in a system to maximize cabling and PoE performance.
Details on Molex requirements for Warranty can be found at: https://www.molexces.com/about-us/our-warranty/