x
earth

CUSTOMIZE YOUR EXPERIENCE

Close
Change Language: English Region: Americas

PowerCat C6A S/FTP LS0H Cable B2ca-s1a,d1,a1

'

Part No: CAA-00437-VL

Region: emea

The PowerCat 6A Shielded Cable is a key component of the PowerCat 6A end-to-end solution. Molex PowerCat 6A S/FTP Cable is specifically designed to support high speed data network applications such as 10-Gigabit Ethernet (10GBASE-T).

The cable is constructed of four screened pairs enclosed in a tin/copper braid, designed to minimize alien crosstalk, and provide excellent signal isolation and electromagnetic interference (EMI) protection. The cable provides high class reaction to fire performance, in accordance with the EN 50575:2014 + A1:2016 EuroClass classification of B2ca-s1a,d1, a1. Molex recommends that the full range of PowerCat 6A Shielded products be used in a system to maximize cabling performance. This system is compliant with ISO/IEC 11801 for the support of 10GBASE-T.

Features & Benefits Technical Info
  • Outstanding signal isolation
  • Compliant with TIA/EIA 568.2-D
  • Enhanced performance 4 pair S/FTP foil and braid screened cable
  • Resistant to alien crosstalk
  • Color coded for ease of termination
  • Reaction to Fire Euroclass: B2ca-s1a, d1, a1

MECHANICAL
Conductor o.d.: 0.560 ± 0.005mm
Conductor material: Solid Bare Copper
Pair Number: 4
Outer diameter: 7.8 ± 0.5m
Shield: Al/Mylar
Braid: Tinned copper

Temperature Range
Installation: -10˚C to + 50˚C
Operation: -40˚C to + 75˚C
Storage: -20˚C to +50˚C
Bend radius installation: 8 x o.d.
Bend radius operation: 6 x o.d.
Pulling force: ≥9.0 Mpa
Sheath: LS0H
Sheath color: Violet RAL 4005
Shipping weight 500m reel: 29.4kg
Cable length tolerance: +/- 5%

ELECTRICAL
Characteristic Impedance Ohm:
1-250 MHz: 100 +/- 15 Ohm
250-500 MHz: 100 +/- 22 Ohm
DC Resistance Ohm/100m max: 9.38
DC Loop Resistance Ohm/100m: 19
Resistance unbalance % max: 5.0
Unbalanced to ground capacitance pf/100m max: 330
Voltage rating (Vdc): <80
NVP nominal: 74%
Delay skew 1-500 OMHz ns/100m max: <45

COMMERCIAL STANDARDS
TIA/EIA-568-C.2-D Category 6A
IEC 61156-5
RoHS Compliant

REACTION TO FIRE
EU Regulation 305/2011 (CPR)
EN 50575:2014+A:2016
Euroclass: B2ca-s2,d1,a1

Fire Propagation Tests
IEC 60332-1-2, IEC 60754-2, IEC 61034-2, EN 50399